AC:1.0/1.0 kV XL -HFFR INSULATED SINGLE CORE SOLAR CABLE
AC:1.0/1.0 kV XL -HFFR INSULATED SINGLE CORE SOLAR CABLE

AC: 1.0/1.0 kV XL -HFFR INSULATED SINGLE CORE SOLAR CABLE

• H1Z2Z2-K

Öznur icon
Code H1Z2Z2-K
Standarts EN 50618
Construction Electrolytic tinned copper, fine stranded class 5 conductor, XL-HFFR cross-linked insulation, XL-HFFR cross-linked outer sheath.
Application Used in solar power systems for connections between solar panels and system components such as inverters. Suitable for installation in cable ducts and cable trays, in indoor and outdoor applications.
Technical Datas Operating temperature is between -40°C and +90°C
Minimum installation temperature is -25°C
Minimum bending radius is 4*D D: Cable’s outer diameter(mm)
  • Product Description
Dimensions & Weights
  Electrical Data
Nominal
cross section
Overall
Diameter
Net Weight
Maximum
permissible
tensile force
Conductor DC resistance at 20 °C (Maximum)

Current carrying capacity at 60°C ambient temperature

On surface (A)
In free air (A)
mm² mm
kg/km
Max. (N)
ohm/km
1.5 4.6 35 23 13,7 29 30
2.5 5.0 45 38 8,21 39 41
4 5.6 60 60 5,09 52 55
6 6.1 80 90 3,39 67 70
10 7.2 124 150 1,95 93 98
16 9.2 195 240 1,24 125 132
25 10.8 286 375 0,795 167 176
35 12.4 395 525 0,565 207 218
50 14.6 545 750 0,393 262 276
70 17.2 745 1050 0,277 330 347
95 19.4 975 1425 0,210 395 416
120 21.5 1230 1800 0,164 464 488
150 24 1558 2250 0,132 538 566
185 27.4 1927 2775 0,108 612 644
240 30.3 2443 3600 0,0817 736 775